Step 1:确认协议与工具
主流 PLC 大多支持 OPC UA(西门子 S7、三菱、欧姆龙等均有 UA 服务端选项)。开源客户端推荐 asyncua:
pip install asyncua
# 快速测试连接
python -c \
"from asyncua import Client; \
c=Client('opc.tcp://192.168.1.50:4840'); c.connect(); \
print('connected'); c.disconnect()"Step 2:读取节点数据
import asyncio
from asyncua import Client
async def read_values():
client = Client("opc.tcp://192.168.1.50:4840")
await client.connect()
try:
# 按节点路径读取(路径需与现场命名空间对应)
node = client.get_node("ns=2;s=Machine1.Temp")
value = await node.read_value()
print(f"Machine1.Temp = {value} °C")
# 批量订阅
handler = SubHandler()
sub = await client.create_subscription(500, handler) # 500ms 周期
await sub.subscribe_data_change(node)
await asyncio.sleep(10)
finally:
await client.disconnect()
asyncio.run(read_values())Step 3:断网缓存与续传
车间网络不稳是常态,采集端必须能断网缓存、恢复续传:
# 断网缓存伪代码
buffer = deque(maxlen=100_000) # 本地环形缓存
def on_data(tag, value):
try:
push_to_mq(tag, value) # 正常推送
except NetworkError:
buffer.append((ts, tag, value)) # 断网先入缓存
def on_reconnect():
while buffer:
push_to_mq(*buffer.popleft()) # 按序补传
time.sleep(0.01) # 限速防冲垮Step 4:只读模式与心跳
① 采集端保持只读,不向 PLC 下发指令——最坏情况断网也不影响产线;
② 每 5 秒心跳,采集端掉线立即告警;
③ 关键设备双网关互备,切换时间控制在秒级;
④ 按数据类型选频率:振动/闭环毫秒级,温度/压力秒级,能耗/统计分钟级。
# 心跳示例
def heartbeat():
while True:
mq.publish("collector/heartbeat", {"ts": now()}, qos=1)
time.sleep(5)现场节点路径(ns/标识符)因 PLC 厂商与配置而异,建议先用 UA Expert 等工具浏览确认后再写代码。